2 Initial data
Таble 1
Initial data |
||||||||
Type of fuel |
The number and power generator, MW |
Quantity and power lines load on the generator voltage, MW |
Consumption for own need in % |
RUSN nominal voltage, kV |
The number of lines and the power loads RUSN, MW |
Continuation of loads, winter-summer |
Nominal voltage of lines to the system, kV |
Number of lines and their length, km |
Fuel oil |
5/63 |
15/6 |
7 |
35 |
2/45 |
160/205 |
110 |
2/90 |
Selected turbogenerator from CGW №1
Table 1 - Main technical characteristics
Type of turbogenerator |
|
ТВФ-9-2У |
ТВС-81У |
Nominal rot. frequency, rpm |
|
3000 |
3000 |
Nominal power |
Full, МV·А |
76,45 |
40 |
Active, MW |
54 |
35 |
|
Nom. voltage, kV |
|
8,3 |
8,3 |
cosφном |
|
0,9 |
0,9 |
Nominal current, kA |
|
6,89 |
4,11 |
Selected transformers from CGW №2:
1 transformer of type TRDNC-40000/35 and 1 transformer TDTN-80000/110;
Table 3- Basic technical data of transformers
Transformer type |
TRNDS-40000/35 |
TDTN-80000/110 |
|
Rated power, MVA |
40 |
80 |
|
Winding voltage, kV |
36,75 |
115 |
110 |
- |
38,5 |
- |
|
10,5 |
11 |
10.5 |
|
Losses, kW |
36 |
64 |
34 |
170 |
365 |
170 |
|
uk, % |
- |
10,5 |
- |
12,7 |
17,5 |
15 |
|
40 |
6,5 |
- |
|
3 Short-circuit currents calculation
We will calculate in relative units. Determine the resistance of the circuit at the base power Sb=1000 МVA
Resistance of generators G1, G2:
Resistance of generator G3:
Define the EMF of the generator G1, G2 and G3:
where I0=1; U0=1; cosφ0=0,85; sinφ0=0,53.
Resistance of transformer Т3:
Resistance of transformers Т1, Т2:
The resistance of the double-circuit power line:
where
-
the resistivity of the line is assumed to be equal to 0,4 Om/km.
Figure 2 - The replacement scheme of the CHPP
Simplification of the substitution scheme:
Figure 3— Simplified scheme
Figure 4 - Simplified scheme for the replacement of CHPPs
The initial value of the periodic component of the SC current
where
and
-
the resulting resistance of the circuit branch and the base current.
Three-phase SC current from generator G1, G2 :
From G3:
From system:
Total SC current :
Determination of shock current of SC:
where ks = 1,94 for generator ТVS-32U3.