2 Calculation of the statistical stability of the electric power system
For a given scheme of the electric power system (Figure 3.1), calculate the dynamic stability for three-phase short-circuit and two-phase short-circuit on the ground on a given line in the presence of an ARE of proportional type on the generators. Catalog data of power system installations:
Table 2.1 - Catalog data of turbogenerator of power station 1
Type |
Sn, VA |
cosϕ |
Q1, Mvar |
Un, kV |
х"d(н) |
хd(н) |
х2(н) |
GD2, t·m2 |
Td0 |
n |
ТGV-345 |
78 |
0,85 |
100 |
10.5 |
0.26 |
1.8 |
0.24 |
15 |
9 |
4 |
Table 2.2 - Catalog data of substation transformers 1
Type |
n |
Sn, MVA |
UnHV, kV |
UnLV, kV |
uk, % |
P |
Pxx |
|
1 |
300 |
45 |
10.5 |
10.5 |
|
|
Table 2.3 - Catalog data of substation transformers 2
Type |
n |
Sn, MVA |
UnHV, kV |
UnLV, kV |
uk, % |
P |
Pxx |
|
1 |
400 |
100 |
10.5 |
10.5 |
|
|
Table 2.4- Parameters of other elements
Power lines, n=2 |
System |
Load |
Ppl=150 MW |
Uc=110 kV |
Рload =350 МW |
cosφ=0,85 |
Sc=234 MVA |
cosφ=0.85 |
Un =15.75 кV |
cos=0.85 |
|
ℓ=100 km |
sin=0.341 |
|
х10=0,37 Оhm/km, |
|
|
r10=0,132 Оhm/km |
|
|
Figure 3.1 - Calculation scheme for option 23
The solution:
1. We compose substitution scheme and apply results of calculations to it.
2. Determine the parameters of the substitution circuit for this we specify basic values (voltage, power).
For the base voltage, we take the voltage on the buses of an equivalent system GS of infinite power (which has an infinite regulating effect of the load, which leads to a constant voltage on the buses of the equivalent system) Ub3 = 10.5 kV. The base power is assumed equal to Sb = 100 MVA.
We define the base voltages for the following steps:
Define the resistance of the elements:
- the equivalent generator G
- at substation 1 (T1):
- at substation 2 (T2):
- resistance of power lines:
We determine the total power of the load and the power flowing along the power lines to the buses of constant voltage:
We determine the voltage of the main stage in relative units:
We form the equivalent circuit on which is applied the obtained calculation values:
Figure 3.4 - The equivalent circuit
3. Calculation of the angular power characteristics for a normal mode
Determine the transient resistance xd’’:
Determine the total reactance
Define the transient EMF:
Let us determine the transverse component of the transient EMF:
Define the transmitted power: