- •Introduction
- •Table of Contents
- •1. Main Data and Outputs
- •1.1 Maximum continuous output
- •1.2 Reference conditions
- •1.3 Operation in inclined position
- •1.4 Dimensions and weights
- •2.2 Loading capacity
- •2.3 Low air temperature
- •2. Operating ranges
- •2.1 Engine operating range
- •2.4 Operation at low load and idling
- •3. Technical Data
- •3.1 Wärtsilä 4L20
- •3.2 Wärtsilä 6L20
- •3.3 Wärtsilä 8L20
- •3.4 Wärtsilä 9L20
- •4. Description of the Engine
- •4.1 Definitions
- •4.2 Main components and systems
- •4.3 Cross sections of the engine
- •4.4 Overhaul intervals and expected lifetimes
- •5. Piping Design, Treatment and Installation
- •5.1 Pipe dimensions
- •5.2 Trace heating
- •5.3 Operating and design pressure
- •5.4 Pipe class
- •5.5 Insulation
- •5.6 Local gauges
- •5.7 Cleaning procedures
- •5.8 Flexible pipe connections
- •5.9 Clamping of pipes
- •6. Fuel Oil System
- •6.1 Acceptable fuel characteristics
- •6.2 Internal fuel oil system
- •6.3 External fuel oil system
- •7. Lubricating Oil System
- •7.1 Lubricating oil requirements
- •7.2 Internal lubricating oil system
- •7.3 External lubricating oil system
- •7.4 Crankcase ventilation system
- •7.5 Flushing instructions
- •8. Compressed Air System
- •8.1 Internal compressed air system
- •8.2 External compressed air system
- •9. Cooling Water System
- •9.1 Water quality
- •9.2 Internal cooling water system
- •9.3 External cooling water system
- •10. Combustion Air System
- •10.1 Engine room ventilation
- •10.2 Combustion air system design
- •11. Exhaust Gas System
- •11.1 Internal exhaust gas system
- •11.2 Exhaust gas outlet
- •11.3 External exhaust gas system
- •12. Turbocharger Cleaning
- •12.1 Turbine cleaning system
- •12.2 Compressor cleaning system
- •13. Exhaust Emissions
- •13.1 Diesel engine exhaust components
- •13.2 Marine exhaust emissions legislation
- •13.3 Methods to reduce exhaust emissions
- •14. Automation System
- •14.1 UNIC C1
- •14.2 UNIC C2
- •14.3 Functions
- •14.4 Alarm and monitoring signals
- •14.5 Electrical consumers
- •15. Foundation
- •15.1 Steel structure design
- •15.2 Mounting of main engines
- •15.3 Mounting of generating sets
- •15.4 Flexible pipe connections
- •16. Vibration and Noise
- •16.1 External forces and couples
- •16.2 Mass moments of inertia
- •16.3 Structure borne noise
- •16.4 Air borne noise
- •17. Power Transmission
- •17.1 Flexible coupling
- •17.2 Clutch
- •17.3 Shaft locking device
- •17.4 Power-take-off from the free end
- •17.5 Input data for torsional vibration calculations
- •17.6 Turning gear
- •18. Engine Room Layout
- •18.1 Crankshaft distances
- •18.2 Space requirements for maintenance
- •18.3 Transportation and storage of spare parts and tools
- •18.4 Required deck area for service work
- •19. Transport Dimensions and Weights
- •19.1 Lifting of engines
- •19.2 Engine components
- •20. Product Guide Attachments
- •21. ANNEX
- •21.1 Unit conversion tables
- •21.2 Collection of drawing symbols used in drawings
Product Guide
9. Cooling Water System
9.3External cooling water system
Figure 9.4 Cooling water system, auxiliary engines operating on HFO and MDO (3V76C5823a)
System components: |
|
|
|
4E05 |
Heater (Preheating unit) |
4P09 |
Transfer pump |
4E08 |
Central cooler |
4S01 |
Air venting |
4N01 |
Preheating unit |
4T04 |
Drain tank |
4P04 |
Circulating pump (Preheating unit) |
4T05 |
Expansion tank |
Pipe connections are listed in section "Internal cooling water system".
Product Guide Wärtsilä 20 - 3/2009 |
69 |
Product Guide
9. Cooling Water System
Figure 9.5 Cooling water system common for ME and AE, mixed LT and HT-circuit, common heatrecovery and preheating for ME and AE (DAAE018225c)
System components |
|
|
|
01 |
L20 genset |
15 |
Lubricating oil cooler, Main engine |
02 |
HT-Circulating pump |
16 |
Ancillary plants |
03 |
LT-Circulating pump |
17 |
Scavenge air cooler, Main engine |
04 |
Air cooler |
18 |
Thermostatic valve HT |
05 |
Oil cooler |
19 |
Thermostatic valve HT, heat recovery/preheating |
06 |
HT-Thermostatic valve |
20 |
HT-Circulating pump, Main engine |
07 |
LT-Thermostatic valve |
21 |
HT-Preheating pump, Main engine + Auxiliary engine |
08 |
Preheating pump, Auxiliary engine |
22 |
HT-Preheater |
09 |
Preheater, Auxiliary engine |
23 |
Heat recovery from HT-circuit, Main engine |
10 |
Central cooler |
24 |
Heat recovery from LT-circuit, Main engine + Auxiliary engine |
11 |
Air venting |
25 |
Alternator cooler |
12 |
Expansion tank |
26 |
Circulating pump |
13 |
LT-Circulating pump |
27 |
Booster heater (optional) |
14 |
LT-Thermostatic valve |
|
|
Pipe connections are listed in section "Internal cooling water system".
70 |
Product Guide Wärtsilä 20 - 3/2009 |
Product Guide
9. Cooling Water System
Figure 9.6 Common cooling water system, split LT and HT-circuit, common heat recovery and preheating (DAAE018600b)
System components: |
|
|
|
01 |
L20 Genset |
16 |
Ancilliary plants |
02 |
HT-Circulating pump |
17 |
Scavenge air cooler, Main engine |
03 |
LT-Circulating pump |
18 |
Thermostatic valve HT |
04 |
Air cooler |
19 |
Thermostatic valve HT, heat recovery/preheating |
05 |
Oil cooler |
20 |
HT-Circulating pump, Main engine |
06 |
HT-Thermostatic valve |
21 |
HT-Preheating pump, Main engine + auxiliary engine |
07 |
LT-Thermostatic valve |
22 |
HT-Preheater |
08 |
Preheating pump, Auxiliary engine |
23 |
Heat recovery form HT-circuit, Main engine |
09 |
Preheater, Auxiliary engine |
24 |
Heat recovery from HT-circuit, Main engine + auxiliary engine |
10 |
Central cooler |
25 |
Alternator cooler |
11 |
Air venting |
26 |
HT-Cooler |
12 |
Expansion tank |
27 |
HT-Expansion tank |
13 |
LT-Circulating pump |
28 |
Circulating pump |
14 |
LT-Thermostatic valve |
29 |
Booster heater (oprional) |
15 |
Lubricating oil cooler, Main engine |
|
|
Pipe connections are listed in section "Internal cooling water system".
Product Guide Wärtsilä 20 - 3/2009 |
71 |
Product Guide
9. Cooling Water System
Figure 9.7 Cooling water system, main engine (3V76C5825a)
System components: |
|
|
|
4E05 |
Heater (Preheating unit) |
4P05 |
Stand-by pump (LT) |
4E08 |
Central cooler |
4P09 |
Transfer pump |
4E10 |
Cooler (Reduction gear) |
4P11 |
Circulating pump (Sea water) |
4F01 |
Suction strainer (Sea water) |
4S01 |
Air venting |
4N01 |
Preheating unit |
4T04 |
Drain tank |
4P03 |
Stand-by pump (HT) |
4T05 |
Expansion tank |
4P04 |
Circulating pump (Preheating unit) |
|
|
Pipe connections are listed in section "Internal cooling water system".
72 |
Product Guide Wärtsilä 20 - 3/2009 |
Product Guide
9. Cooling Water System
Figure 9.8 Cooling water system, HFO engines with evaporator (3V76C5826a)
System components: |
|
|
|
4E05 |
Heater (Preheating unit) |
4P09 |
Transfer pump |
4E08 |
Central cooler |
4S01 |
Air venting |
4N01 |
Preheating unit |
4T04 |
Drain tank |
4N02 |
Evaporator unit |
4T05 |
Expansion tank |
4P04 |
Circulating pump (Preheating unit) |
4V02 Thermostatic valve (Heat recovery) |
|
Pipe connections are listed in section "Internal cooling water system".
Product Guide Wärtsilä 20 - 3/2009 |
73 |
Product Guide
9. Cooling Water System
Figure 9.9 Cooling water system, MDF engines with evaporator (3V76C5827a)
System components: |
|
|
|
4E05 |
Heater (Preheating unit) |
4S01 Air venting |
|
4E08 |
Central cooler |
4T04 |
Drain tank |
4N01 |
Preheating unit |
4T05 |
Expansion tank |
4N02 |
Evaporator unit |
4V02 |
Thermostatic valve (Heat recovery) |
4P04 |
Circulating pump (Preheating unit) |
4V08 |
Thermostatic valve (LT) |
4P09 |
Transfer pump |
|
|
Pipe connections are listed in section "Internal cooling water system".
It is recommended to divide the engines into several circuits in multi-engine installations. One reason is of course redundancy, but it is also easier to tune the individual flows in a smaller system. Malfunction due to entrained gases, or loss of cooling water in case of large leaks can also be limited. In some installations it can be desirable to separate the HT circuit from the LT circuit with a heat exchanger.
The external system shall be designed so that flows, pressures and temperatures are close to the nominal values in Technical data and the cooling water is properly de-aerated.
Pipes with galvanized inner surfaces are not allowed in the fresh water cooling system. Some cooling water additives react with zinc, forming harmful sludge. Zinc also becomes nobler than iron at elevated temperatures, which causes severe corrosion of engine components.
Ships (with ice class) designed for cold sea-water should have provisions for recirculation back to the sea chest from the central cooler:
74 |
Product Guide Wärtsilä 20 - 3/2009 |
Product Guide
9. Cooling Water System
•For melting of ice and slush, to avoid clogging of the sea water strainer
•To enhance the temperature control of the LT water, by increasing the seawater temperature
9.3.1Stand-by circulation pumps (4P03, 4P05)
Stand-by pumps should be of centrifugal type and electrically driven. Required capacities and delivery pressures are stated in Technical data.
NOTE! Some classification societies require that spare pumps are carried onboard even though the ship has multiple engines. Stand-by pumps can in such case be worth considering also for this type of application.
9.3.2 Sea water pump (4P11)
The capacity of electrically driven sea water pumps is determined by the type of coolers and the amount of heat to be dissipated.
Significant energy savings can be achieved in most installations with frequency control of electrically driven sea water pumps. Minimum flow velocity (fouling) and maximum sea water temperature (salt deposits) are however issues to consider.
9.3.3 Temperature control valve for central cooler (4V08)
When it is desired to utilize the engine driven LT-pump for cooling of external equipment, e.g. a reduction or a generator, there must be a common LT temperature control valve in the external system, instead of an individual valve for each engine. The common LT temperature control valve is installed after the central cooler and controls the temperature of the water before the engine and the external equipment, by partly bypassing the central cooler. The valve can be either direct acting or electrically actuated.
The set-point of the temperature control valve 4V08 is 38 ºC in the type of system described above.
Engines operating on HFO must have individual LT temperature control valves. A separate pump is required for the external equipment in such case, and the set-point of 4V08 can be lower than 38 ºC if necessary.
9.3.4 Fresh water central cooler (4E08)
The fresh water cooler can be of either plate, tube or box cooler type. Plate coolers are most common. Several engines can share the same cooler.
It can be necessary to compensate a high flow resistance in the circuit with a smaller pressure drop over the central cooler.
The flow to the fresh water cooler must be calculated case by case based on how the circuit is designed.
In case the fresh water central cooler is used for combined LT and HT water flows in a parallel system the total flow can be calculated with the following formula:
where: |
|
q = |
total fresh water flow [m³/h] |
qLT = |
nominal LT pump capacity[m³/h] |
Φ = |
heat dissipated to HT water [kW] |
Tout = |
HT water temperature after engine (91°C) |
Tin = |
HT water temperature after cooler (38°C) |
Design data: |
|
Fresh water flow |
see chapter Technical Data |
Heat to be dissipated |
see chapter Technical Data |
Pressure drop on fresh water side |
max. 60 kPa (0.6 bar) |
Sea-water flow |
acc. to cooler manufacturer, normally 1.2 - 1.5 x the fresh water flow |
Product Guide Wärtsilä 20 - 3/2009 |
75 |
Product Guide
9. Cooling Water System
Design data: |
|
Pressure drop on sea-water side, norm. |
acc. to pump head, normally 80 - 140 kPa (0.8 - 1.4 bar) |
Fresh water temperature after cooler |
max. 38°C |
Margin (heat rate, fouling) |
15% |
Figure 9.10 Central cooler, main dimensions (4V47E0188b)
|
|
|
Cooling water |
|
Sea water |
Dimension [mm] |
Weight [kg] |
|||||
Engine |
[rpm] |
Flow |
Tcw, in |
Tcw, out |
Flow |
Tsw, in |
Tsw, out |
A |
B |
C |
Dry |
Wet |
|
|
[m³/h] |
[°C] |
[°C] |
[m³/h] |
[°C] |
[°C] |
|
|
|
|
|
W 4L20 |
1000 |
27 |
54.3 |
38 |
36 |
32 |
44.3 |
106 |
505 |
695 |
275 |
298 |
W 6L20 |
1000 |
40 |
53.3 |
38 |
53 |
32 |
43.5 |
150 |
655 |
845 |
288 |
321 |
W 8L20 |
1000 |
53 |
53.6 |
38 |
71 |
32 |
43.8 |
198 |
655 |
845 |
298 |
341 |
W 9L20 |
1000 |
59 |
53.7 |
38 |
80 |
32 |
43.8 |
221 |
905 |
1095 |
305 |
354 |
As an alternative for the central coolers of the plate or of the tube type a box cooler can be installed. The principle of box cooling is very simple. Cooling water is forced through a U-tube-bundle, which is placed in a sea-chest having inletand outlet-grids. Cooling effect is reached by natural circulation of the surrounding water. The outboard water is warmed up and rises by its lower density, thus causing a natural upward circulation flow which removes the heat.
Box cooling has the advantage that no raw water system is needed, and box coolers are less sensitive for fouling and therefor well suited for shallow or muddy waters.
9.3.5 Waste heat recovery
The waste heat in the HT cooling water can be used for fresh water production, central heating, tank heating etc. The system should in such case be provided with a temperature control valve to avoid unnecessary cooling, as shown in the example diagrams. With this arrangement the HT water flow through the heat recovery can be increased.
The heat available from HT cooling water is affected by ambient conditions. It should also be taken into account that the recoverable heat is reduced by circulation to the expansion tank, radiation from piping and leakages in temperature control valves.
76 |
Product Guide Wärtsilä 20 - 3/2009 |
Product Guide
9. Cooling Water System
9.3.6 Air venting
Air may be entrained in the system after an overhaul, or a leak may continuously add air or gas into the system. The engine is equipped with vent pipes to evacuate air from the cooling water circuits. The vent pipes should be drawn separately to the expansion tank from each connection on the engine.
Venting pipes to the expansion tank are to be installed at all high points in the piping system, where air or gas can accumulate.
The vent pipes must be continuously rising.
9.3.7 Expansion tank (4T05)
The expansion tank compensates for thermal expansion of the coolant, serves for venting of the circuits and provides a sufficient static pressure for the circulating pumps.
Design data: |
|
Pressure from the expansion tank at pump inlet |
70 - 150 kPa (0.7...1.5 bar) |
Volume |
min. 10% of the total system volume |
NOTE! The maximum pressure at the engine must not be exceeded in case an electrically driven pump is installed significantly higher than the engine.
Concerning the water volume in the engine, see chapter Technical data.
The expansion tank should be equipped with an inspection hatch, a level gauge, a low level alarm and necessary means for dosing of cooling water additives.
The vent pipes should enter the tank below the water level. The vent pipes must be drawn separately to the tank (see air venting) and the pipes should be provided with labels at the expansion tank.
The balance pipe down from the expansion tank must be dimensioned for a flow velocity not exceeding 1.0...1.5 m/s in order to ensure the required pressure at the pump inlet with engines running. The flow through the pipe depends on the number of vent pipes to the tank and the size of the orifices in the vent pipes. The table below can be used for guidance.
Table 9.2 Minimum diameter of balance pipe
Nominal pipe size |
Max. flow velocity |
Max. number of vent pipes |
|
(m/s) |
with ø 5 mm orifice |
DN 32 |
1.1 |
3 |
DN 40 |
1.2 |
6 |
DN 50 |
1.3 |
10 |
DN 65 |
1.4 |
17 |
9.3.8 Drain tank (4T04)
It is recommended to collect the cooling water with additives in a drain tank, when the system has to be drained for maintenance work. A pump should be provided so that the cooling water can be pumped back into the system and reused.
Concerning the water volume in the engine, see chapter Technical data. The water volume in the LT circuit of the engine is small.
9.3.9 Preheating
The cooling water circulating through the cylinders must be preheated to at least 60 ºC, preferably 70 ºC. This is an absolute requirement for installations that are designed to operate on heavy fuel, but strongly recommended also for engines that operate exclusively on marine diesel fuel.
The energy required for preheating of the HT cooling water can be supplied by a separate source or by a running engine, often a combination of both. In all cases a separate circulating pump must be used. It is common to use the heat from running auxiliary engines for preheating of main engines. In installations with
Product Guide Wärtsilä 20 - 3/2009 |
77 |
Product Guide
9. Cooling Water System
several main engines the capacity of the separate heat source can be dimensioned for preheating of two engines, provided that this is acceptable for the operation of the ship. If the cooling water circuits are separated from each other, the energy is transferred over a heat exchanger.
Heater (4E05)
The energy source of the heater can be electric power, steam or thermal oil.
It is recommended to heat the HT water to a temperature near the normal operating temperature. The heating power determines the required time to heat up the engine from cold condition.
The minimum required heating power is 2 kW/cyl, which makes it possible to warm up the engine from 20 ºC to 60...70 ºC in 10-15 hours. The required heating power for shorter heating time can be estimated with the formula below. About 1 kW/cyl is required to keep a hot engine warm.
Design data: |
|
Preheating temperature |
min. 60°C |
Required heating power |
2 kW/cyl |
Heating power to keep hot engine warm |
1 kW/cyl |
Required heating power to heat up the engine, see formula below:
where: |
|
P = |
Preheater output [kW] |
T1 = |
Preheating temperature = 60...70 °C |
T0 = |
Ambient temperature [°C] |
meng = |
Engine weight [ton] |
VLO = |
Lubricating oil volume [m3] (wet sump engines only) |
VFW = |
HT water volume [m3] |
t = |
Preheating time [h] |
keng = |
Engine specific coefficient = 0.5 kW |
ncyl = |
Number of cylinders |
The formula above should not be used for P < 2 kW/cyl
Circulation pump for preheater (4P04)
Design data: |
|
Capacity |
0.3 m3/h per cylinder |
Delivery pressure |
80 kPa (0.8 bar) |
Preheating unit (4N01)
A complete preheating unit can be supplied. The unit comprises:
•Electric or steam heaters
•Circulating pump
•Control cabinet for heaters and pump
•Set of thermometers
•Non-return valve
•Safety valve
78 |
Product Guide Wärtsilä 20 - 3/2009 |
Product Guide
9. Cooling Water System
Figure 9.11 Preheating unit, electric (3V60L0653a)
Heater capacity |
Pump capacity |
Weight |
Pipe connections |
|
|
Dimensions |
|
|
kW |
m3 / h |
kg |
Inlet / Outlet |
A |
B |
C |
D |
E |
7.5 |
3 |
75 |
DN40 |
1050 |
720 |
610 |
190 |
425 |
12 |
3 |
93 |
DN40 |
1050 |
550 |
660 |
240 |
450 |
15 |
3 |
93 |
DN40 |
1050 |
720 |
660 |
240 |
450 |
18 |
3 |
95 |
DN40 |
1250 |
900 |
660 |
240 |
450 |
22.5 |
8 |
100 |
DN40 |
1050 |
720 |
700 |
290 |
475 |
27 |
8 |
103 |
DN40 |
1250 |
900 |
700 |
290 |
475 |
30 |
8 |
105 |
DN40 |
1050 |
720 |
700 |
290 |
475 |
36 |
8 |
125 |
DN40 |
1250 |
900 |
700 |
290 |
475 |
45 |
8 |
145 |
DN40 |
1250 |
720 |
755 |
350 |
505 |
54 |
8 |
150 |
DN40 |
1250 |
900 |
755 |
350 |
505 |
9.3.10 Throttles
Throttles (orifices) are to be installed in all by-pass lines to ensure balanced operating conditions for temperature control valves. Throttles must also be installed wherever it is necessary to balance the waterflow between alternate flow paths.
9.3.11 Thermometers and pressure gauges
Local thermometers should be installed wherever there is a temperature change, i.e. before and after heat exchangers etc.
Local pressure gauges should be installed on the suction and discharge side of each pump.