Visit the Alpha website at www.alpha.ca for the latest manual and product downloads

6.3.3.4Limit Power Save Log

The logs “Power Save Restart” and “Power Save Shutdown” are limited to one every 24 hours.

Figure 33–Power Save options

6.3.4Phase Mapping

This feature will enable the user to assign or map a rectifier per input signal for individual phase voltage readings:

Assign/map a rectifier per Phase

R, S, and T (radio buttons) for the respective signal

Tap Locate and the LEDs of the selected rectifier will flash to enable the user to determine the phase connection

Discard changes and return to previous screen

Accept changes and return to previous screen

Figure 34–Phase Mapping (rectifiers) window

6.4Batteries

This menu category consists of battery controls. Parameters can be set/accessed, such as automatic temperature compensation, auto equalize and battery current (I) limit.

See Standard Features chapter for an explanation of temperature compensation and lead acid battery auto equalization.

6.4.1Temperature Compensation (Temp Comp)

6.4.1.1Enable

This menu item enables the Supervisor to control the CXC’s temperature compensation feature. Automatic battery temperature compensation may be enabled in equalize mode independently from float mode. Battery Properties section must be completed to enable this feature.

6.4.1.2Upper/Lower Breakpoints

This menu item enables the Supervisor to program the temperature at which automatic voltage changes in the system will cease. There are voltage and temperature values for both breakpoints (upper and lower). However, note that the Upper Breakpoint refers to the higher temperature at which automatic voltage changes will cease. Lower Breakpoint refers to the lower temperature. Reversing these (placing the lower temperature as the “Upper Breakpoint” and the lower temperature as the “Lower Breakpoint” will not work.

0350046-J0 Rev C