The following menu items enable the Supervisor to configure the alarms associated with each analog input.

6.5.3.4Current Alarms

Battery Current High

This menu item enables the Supervisor to program the setting for the battery amps alarm. When the total current to the battery exceeds this setting, the alarm is activated and the message BATTERY CURRENT HIGH is displayed on the GUI.

Load Current High

This menu item enables the Supervisor to program the setting for the load amps alarm. When the current to the load has exceeded this setting, an alarm is activated and the message LOAD CURRENT HIGH is displayed on the GUI.

6.5.3.5Voltage Alarms

AC Mains High

This menu item enables the Supervisor to program the setting for the mains high alarm. When the AC exceeds this setting, the alarm is activated and the message AC MAINS HIGH is displayed on the GUI.

AC Mains Low

This menu item enables the Supervisor to program the setting for the mains low alarm. When the AC input to the power system falls below this setting, the alarm is activated and the message AC MAINS LOW is displayed on the GUI.

High Voltage [1-2]

When the power system’s DC voltage exceeds the Supervisor-specified value, the alarm is activated and the message HIGH VOLTAGE 1 (or 2) is displayed.

Low Voltage [1-2]

When the power system’s DC voltage falls below the Supervisor-specified value, the alarm is activated and the message LOW VOLTAGE 1 (or 2) is displayed.

Midpoint Monitor [1-5]

This menu item enables the Supervisor to program the setting for the midpoint monitor voltage alarm. When the voltage reading (1 through 5) exceeds this setting (from the midpoint), the alarm is activated and the message MIDPOINT MONITOR 1 (or 2-5) is displayed.

6.5.3.6Battery Alarms

Battery Runtime Low

The Supervisor can specify, in hours, when the battery runtime alarm activates with respect to the hours remaining in the battery runtime prediction.

Battery Capacity (Remaining) Low

This menu item enables the Supervisor to set the battery capacity alarm trigger point as a percentage. When the capacity of the battery is depleted to this specified value, the capacity alarm is activated.

Battery Overtemp

This menu item enables the Supervisor to set the temperature at which the battery over temperature alarm will activate.

Battery On Discharge

This menu item enables the Supervisor to set an alarm when the battery is on discharge; e.g., during AC Fail or BT mode.

Battery Test

This menu item enables the Supervisor to set an alarm when the Battery Test is in progress.

Boost Mode

This menu item enables the Supervisor to set an alarm when the BST mode is activated.

6.5.3.7Temperature Alarms

Temp Sensor Fail [1-4]

This menu item enables the Supervisor to set an alarm when any temperature sensor fails.