- •1 Introduction
- •1.1 Scope of the Manual
- •1.3.7 New Features (since version 1.8)
- •1.3.8 New Feature for version 1.93
- •1.3.9 New Feature for version 1.95
- •1.3.10 New Feature for version 1.97
- •1.3.11 New Features (since version 1.97)
- •1.3.12 New Features since version 2.03
- •1.3 Software Overview
- •1.3.1 New Features since version 1.2
- •1.3.2 New Features since version 1.3
- •1.3.3 New Features (since version 1.4)
- •1.3.4 New Features (since version 1.5)
- •1.3.5 New Features since version 1.6
- •1.3.6 New Features (since version 1.7)
- •1.3.13 Alarm Tone New Features since version 2.04
- •1.3.14 New Features since version 2.05
- •2 Quick Start
- •2.1 Applying Startup Power
- •2.3.1 Converter and Rectifier Tips
- •2.3.2 Cordex Controller Tips
- •3 Standard Features
- •3.1 Password Security
- •3.2 Software Configuration Loading and Updates
- •3.3 Mixed Rectifier System
- •3.4 Safe Voltage
- •3.5 Power Save
- •3.6 Battery Temperature Compensation
- •3.6.1 Theory of Battery Temperature Compensation
- •3.6.2 Operation of Battery Temperature Compensation
- •3.7 Battery Auto Equalization
- •3.7.1 Battery Charge Auto Equalize
- •3.7.2 Periodic Auto Equalize
- •3.7.3 Battery Current Termination (BCT) Equalize
- •3.8 Battery Monitor and Charge Current Control
- •3.9 Low Voltage Disconnect Operation
- •3.10 Signals Management
- •3.11 Statistics and Historical Data
- •3.11.1 Analog Statistics
- •3.11.2 Battery Log
- •3.11.3 Event Log
- •3.11.4 Data Logging
- •4 Operation
- •4.1 Startup and Reset Procedure
- •4.2 Normal Operation
- •4.2.1 Activation/Tapping
- •4.2.2 LCD Touch Screen Calibration
- •4.3 Mode Status (active area) and Temp Comp Indication
- •4.3.1 Float (FL) Mode
- •4.3.2 Equalize (EQ) Mode
- •4.3.3 Boost (BST) Mode
- •4.3.4 Battery Discharge Test or Battery Test (BT) Mode
- •4.3.4.1 Definitions
- •4.3.4.2 Manual Activation
- •4.3.4.4 Tips on Using the BT Mode
- •4.3.4.5 BT Initiation
- •4.3.4.6 Activity During BT Mode
- •4.3.4.7 AC Failure During BT Mode
- •4.3.4.8 Addition of Rectifiers During BT Mode
- •4.3.4.9 Conditions to Watch for During BT Mode
- •4.3.4.10 Canceling BT Mode
- •4.3.4.11 Battery Discharge Test Completion
- •4.3.4.12 Remote BT Mode
- •4.4 Rectifiers (and Converters) Information (active area)
- •4.4.1 Inventory Update
- •4.4.2 Rectifier Report (Converter Report similar)
- •4.5 Analog Signals Display (active area)
- •4.5.1 Controller Signals
- •4.5.2 Analog Inputs
- •4.5.3 Digital Inputs
- •4.5.4 Rectifier Signals
- •4.5.5 Custom Signals
- •4.5.6 Converter Signals
- •4.5.7 Counter
- •4.5.8 Timers
- •4.5.9 ADIO Signals
- •4.6 Alarm Indication (active area)
- •4.6.1 Cutoff All Alarms
- •4.6.2 Alarm History
- •4.7 Home Icon (active area)
- •4.7.1 Login (password entry)
- •4.7.2 Contrast Adjustment of the GUI
- •4.7.3 Reset
- •4.7.4 Language Selection
- •4.8 Date and Time (active area)
- •4.9 Saving Settings
- •4.10 Overview of Web Interface
- •4.10.1 SNTP (Simple Network Time Protocol)
- •5 Menu Navigation and Sample Programming
- •5.1 Menu Navigation
- •5.1.1 Option to Logout
- •5.1.2 Option to Save
- •5.1.4 Backlight Timeout
- •5.1.5 Virtual Numeric Keypad
- •5.2 Basic Programming Example
- •5.3 Advanced Programming
- •6.1.2 CAN Device Firmware (FW) Upgrade [CX Series only]
- •6.1.3 Set ADIO Module Number
- •6 Menu Structure, Programming and Adjustments
- •6.1 System Info
- •6.1.1 System Configuration
- •6.1.4 Site Information
- •6.1.4.1 System Number
- •6.1.4.2 System Serial
- •6.1.5 Contact Information
- •6.1.6 Temperature Units
- •6.1.7 Factory Information
- •6.1.8 User Inventory (Web Interface Only)
- •6.1.9 System Inventory (Web Interface Only)
- •6.2 Converters
- •6.2.1 Converter Report
- •6.2.2 Configure Settings
- •6.3 Rectifiers
- •6.3.1 Rectifier Report
- •6.3.2 Configure Settings
- •6.3.2.1 Float (FL) Voltage
- •6.3.2.2 Equalize (EQ) Voltage
- •6.3.2.3 Battery Test (BT) Voltage
- •6.3.2.4 Safe Voltage
- •6.3.2.5 OVP Voltage
- •6.3.2.6 Low Voltage Alarm (LVA)
- •6.3.2.7 High Voltage Alarm (HVA)
- •6.3.2.8 Current Limit (CL)
- •6.3.2.9 Power Limit (PL)
- •6.3.2.10 EQ Timeout
- •6.3.2.11 BT Timeout
- •6.3.2.12 Slope (Pathfinder rectifiers only)
- •6.3.2.13 Backlight Timeout (Pathfinder rectifiers w/LCD only)
- •6.3.2.14 Security Code (Pathfinder rectifiers w/LCD only)
- •6.3.2.15 Module Start Delay
- •6.3.2.16 System Start Delay
- •6.3.2.17 Soft Start Ramp Rate (Cordex rectifiers only)
- •6.3.2.18 Temp Display Scale (Pathfinder rectifiers w/LCD only)
- •6.3.2.19 Check to Enable
- •6.3.3 Power Save
- •6.3.3.1 Enable
- •6.3.3.2 Redundant Rectifiers
- •6.3.3.3 Max (Maximum) Power Usage
- •6.3.3.4 Limit Power Save Log
- •6.3.4 Phase Mapping
- •6.4 Batteries
- •6.4.1 Temperature Compensation (Temp Comp)
- •6.4.1.1 Enable
- •6.4.1.2 Upper/Lower Breakpoints
- •6.4.2 Auto Equalize
- •6.4.2.1 EQ Duration
- •Enable
- •Interval
- •Enable
- •Activation (High Voltage) Threshold
- •Arming (Low Voltage) Threshold
- •6.4.3 Charge Current Control (CCC)
- •6.4.3.1 Enable
- •6.4.3.2 Charge Rate Limit
- •6.4.3.3 Enable Dynamic CCC
- •6.4.4 Battery Monitor
- •6.4.4.1 Enable
- •6.4.4.2 Load Type
- •6.4.4.3 Disconnect Voltage
- •6.4.4.4 Reset Battery Monitor
- •6.4.5 Battery (Discharge) Test
- •6.4.5.1 BT End Voltage
- •Rectifier BT Voltage (identical to 6.3.2.3 – a change in one alters the other)
- •Rectifier BT Timeout (identical to 6.3.2.11 – a change in one alters the other)
- •6.4.5.2 Auto-BT
- •Enable
- •Interval
- •6.4.5.3 Remote BT Mode
- •Enable
- •Remote BT (Custom 1-20)
- •6.4.6 Battery Current Termination (BCT) Equalize
- •6.4.6.1 Enable
- •6.4.6.2 Duration
- •6.4.6.3 BC Threshold
- •6.4.7 Boost (BST) Mode
- •6.4.7.1 Enable
- •6.4.7.2 Voltage
- •6.4.7.3 Timeout
- •6.4.7.4 Inhibit
- •6.4.8 Battery Properties
- •6.4.8.2 Capacity Calibration
- •6.4.8.3 Open Circuit Voltage
- •6.4.8.4 Peukert Number
- •Peukert Calculator
- •6.4.8.5 Temp Comp Slope
- •6.4.8.6 Number of Cells
- •6.4.9 Battery Information
- •6.5 Alarms
- •6.5.1 Definitions
- •6.5.2 Alarm Icons
- •6.5.3 Configure Alarms
- •6.5.3.1 Overview of Output Relay Channels and Configuration
- •6.5.3.2 Rectifier Alarms
- •Rectifier Fail
- •Rectifier Minor
- •Rect. Major Fail Count
- •Rect. Minor Fail Count
- •Rectifier Lockout (Pathfinder series only)
- •Out of Tolerance
- •Rect. Comms Lost
- •Rect. Equalize Activated
- •Rect. AC Mains Fail
- •Max Rectifiers Exceeded
- •Fan Fail Alarm (for Fan Cooled Systems)
- •Power Save
- •Urgent AC Mains Fail
- •6.5.3.3 Digital Alarms
- •6.5.3.4 Current Alarms
- •Battery Current High
- •Load Current High
- •6.5.3.5 Voltage Alarms
- •AC Mains High
- •AC Mains Low
- •High Voltage [1-2]
- •Low Voltage [1-2]
- •Midpoint Monitor [1-5]
- •6.5.3.6 Battery Alarms
- •Battery Runtime Low
- •Battery Capacity (Remaining) Low
- •Battery Overtemp
- •Battery On Discharge
- •Battery Test
- •Boost Mode
- •6.5.3.7 Temperature Alarms
- •Temp Sensor Fail [1-4]
- •TC Sensor Fail
- •6.5.3.8 Miscellaneous Alarms
- •Real Time Clock Error
- •Invalid Device Firmware
- •Ground Fault Detected (High Voltage CXC only)
- •Improper Controller Shutdown
- •Invalid Battery Voltage
- •System Major
- •System Minor
- •6.5.3.9 ADIO Alarms
- •Signal and a Numeric Value Selected
- •Scheduler Usage
- •6.5.3.11 Converter Alarms
- •Converter Fail
- •Converter Minor
- •Conv. Major Fail Count
- •Conv. Minor Fail Count
- •Conv. Out of Tolerance
- •Conv. Comms Lost
- •Conv. Input Voltage Fail
- •Conv. Fan Fail
- •Conv. Load Current High
- •Conv. Low Output Voltage
- •Conv. High Output Voltage
- •6.5.4 ADIO Alarms Detail
- •6.5.4.1 View Details
- •6.5.5 Alarm Hysteresis
- •6.5.5.1 Voltage
- •6.5.5.2 Time
- •6.5.6 Alarm Tone
- •6.5.7 Configure ALCO
- •6.5.7.1 ALCO Duration
- •6.5.7.2 Enable ALCO Duration
- •6.5.7.3 Silence Buzzer
- •6.5.7.4 Revert Relays
- •6.5.7.5 Stop Sending Email
- •6.5.7.6 Stop Sending SNMP Traps
- •6.6 Signals
- •6.6.1 Calibrate Analog Inputs
- •6.6.1.1 Analog Inputs
- •Definitions
- •Calibration
- •Static Calibration
- •6.6.2 Configure Signals
- •6.6.2.1 Controller Signals
- •Definitions
- •6.6.2.2 Analog Inputs
- •6.6.2.3 Digital Inputs
- •6.6.2.4 Rectifier Signals
- •6.6.2.5 Custom Signals
- •6.6.2.6 Examples of Signal Configuration and Customization
- •Example One – Configure Signal and Customize Signal Equation
- •Example Two – Configure AC Mains
- •Example Three – Configure (Battery Temperature sensors)
- •Example Four – Configure ADIO01 (Shunt MUX)
- •Example Five – Midpoint Voltage Error
- •6.6.2.7 Midnight Rollover
- •Example
- •6.6.2.8 Converter Signals
- •Re-configurable System Load Current and System Battery Voltage
- •Recommendation For Converter Redundancy
- •6.6.2.9 Counter
- •6.6.2.10 Timers
- •6.6.2.11 ADIO Signals
- •6.6.3 Data Logging (Web Interface Only)
- •6.6.3.1 Configure Data Logging
- •6.6.3.2 Starting/Stopping Data Logging
- •6.6.3.3 Retrieve Logs
- •6.6.3.4 Example One – Logging Three Phase Voltage Input (Rectifier System)
- •6.6.3.5 Example Two – Battery System
- •6.6.3.6 Example Three – Generator Voltage
- •6.6.4 ADIO Device Configuration (Web Interface Only)
- •6.7 Controls
- •6.7.1 LVD Control (USE WITH CAUTION)
- •6.7.1.1 DOD Activation
- •6.7.2 LVD Inhibit
- •6.7.3 HVSD
- •6.7.4 CEMF
- •6.7.4.1 Bypass Voltage
- •6.8 Communications
- •6.8.1 Port Status (Web Interface Only)
- •6.8.2 IP Information
- •6.8.3 IP Address (“Ethernet” per web interface)
- •6.8.3.1 CXCI IP Address Reset and Startup
- •6.8.4 Modem (“PPP Connection Device/Rear Modem Port” per web interface)
- •6.8.4.1 Modem Init String
- •6.8.5 Craft Port (“PPP Connection Device/Front Craft Port” per web interface)
- •6.8.6 Web Settings
- •6.8.7 Master SNMP Destination (Web Interface Only)
- •6.8.8 SNMP Multiple Community Names (Web Interface Only)
- •6.8.9 Event Notification Destination (Web Interface Only)
- •6.9 Hardware
- •6.9.1 Configure Relays
- •6.9.2 Test Relays
- •6.9.3 Test Modem (Web Interface only)
- •6.10 Logs & Files (Web Interface only)
- •6.10.1 Retrieve Logs
- •6.10.2 Manage Configuration File
- •6.10.2.1 Printing Custom Site Configuration
- •6.10.3 Manage Dynamic (Editable) Text Files
- •6.10.4 Manage Language Files
- •6.10.5 Retrieve Diagnostic File
- •6.11 Supervisor
- •6.11.1 Change Password
- •7 Advanced Programming
- •7.1 Example: Customize
- •7.2 Equation Builder Keypads
- •7.3 Tips on Programming
- •8 CXC Communications Menu Parameters
- •8.1 Ethernet Port Configuration
- •8.1.1 About IP Addresses
- •8.1.1.1 Static IP Address
- •8.1.1.2 Dynamic IP Address
- •8.1.1.3 Subnet Mask
- •8.1.1.4 Default Gateway
- •8.1.1.5 DHCP (Dynamic Host Configuration Protocol) Servers
- •8.1.2 IP Information
- •8.1.3 Configuring IP Address Settings
- •8.1.3.1 Obtain Address Automatically
- •8.1.3.2 Static Settings
- •IP Address
- •Subnet Mask
- •Gateway
- •8.2 PPP Connection Devices
- •8.2.1 Front Craft Port
- •8.2.2 Rear Modem Port
- •8.3 Rear Port Configuration
- •8.3.1 Internal Modem Support
- •8.3.2 External Modem Support
- •8.3.3 Null Modem Direct Cable Connection Support
- •8.3.4 Configuring Rear Modem Port Settings (CXCP or CXCR only)
- •8.3.4.1 Internal Modem
- •8.3.4.2 External Modem
- •8.3.4.3 NULL Modem
- •9 Remote Communications
- •9.1 Establishing a Network Connection via a Crossover Cable
- •9.1.1 Support for CXCI
- •9.2 PPP Serial Data Connection
- •9.2.1 Starting Networking Wizard
- •9.2.2 Network Connection Wizard
- •Host or Guest? Page
- •Select a Device Page
- •Connection Availability Page
- •Connection Name Page
- •9.2.3 Direct Connection Properties
- •General Tab
- •Options Tab
- •Security Tab
- •Networking Tab
- •Sharing Tab
- •9.2.3.1 Modem Configuration
- •9.2.4 Phone and Modem Options
- •9.2.5 Connect Direct Connection
- •9.2.6 Dial the Modem and Connect to the CXC
- •9.3 Modem Connection
- •9.3.1 Controller Setup
- •9.3.2 Computer Setup
- •9.3.3 CXC Modem Test Feature (via Web interface only)
- •10 Simple Network Management Protocol (SNMP)
- •10.1 Overview
- •10.1.1 Outline of the SNMP Protocol
- •10.1.2 Underlying Communication Protocols
- •10.1.3 Typical UDP Transport
- •10.1.4 Variable Binding (VarBind)
- •10.2 Network Manager MIB Files
- •10.3 Communication Configuration
- •10.3.1 SNMP Multiple Community Names
- •10.3.2 SNMP Trap Recovery
- •10.3.3 Event Notification Destination – Multiple SNMP and SMTP Destinations
- •10.3.3.1 Master SNMP Destination
- •10.3.3.2 Inform Settings (Trap Acknowledge)
- •11 Factory Ranges and Defaults
- •12 Modbus® Communications Protocol
- •13 Trouble-shooting
- •13.1 Technical Support
- •14 Acronyms and Definitions
- •Index
Refer to the back of this manual for Factory Service and Technical Support contact information
TC Sensor Fail
This menu item enables the Supervisor to set an alarm when a sensor enabled for Temp Comp fails.
6.5.3.8Miscellaneous Alarms
Select heading to list
associated menu items
Select menu item to configure
Tap Configure to edit |
|
|
|
Accept changes and |
selected menu item |
|
|
|
|
|
|
|
return to previous screen |
|
|
|
|
||
|
|
|
|
Figure 42–Miscellaneous Alarms window showing menu items
Real Time Clock Error
This menu item enables the Supervisor to set an alarm when any change to the CXC’s clock occurs; due to a battery failure or the real time clock itself failing. The alarm will become active whenever the date is before Jan. 1, 2000 or after Dec. 31, 2030.
Invalid Device Firmware
This menu item enables the Supervisor to set an alarm in the event that the firmware of a device (e.g. Cordex rectifier) has become corrupt and is no longer functioning.
Ground Fault Detected (High Voltage CXC only)
This menu item enables the Supervisor to set the value at which the ground fault detected alarm will activate. The default value is +/-5mA.
Improper Controller Shutdown
This menu item enables the Supervisor to set an alarm in the event that the firmware of the controller has become corrupt and is no longer functioning.
Invalid Battery Voltage
This menu item enables the Supervisor to set an alarm when the charging voltage is invalid; e.g., in the event that the sense leads have become disconnected. The alarm activates when the charge volts signal drops below 5V and halts all control of the system that relies on this signal. If activated (enabled) an entry will be made in the event log.
System Major
This menu item enables the Supervisor to map a relay to the power system major alarm, which is activated if there are one or more active MAJOR alarms. A pull-down menu with scroll bars may be used for navigation.
System Minor
This menu item enables the Supervisor to map a relay to the power system minor alarm, which is activated if there are one or more active MINOR alarms. A pull-down menu with scroll bars may be used for navigation.
6.5.3.9ADIO Alarms
This menu item enables the Supervisor to configure the alarms associated with each ADIO device. Events occurring on one of the inputs can be programmed to the output alarm relays using the programming feature for the relay contacts similar to other alarms.
User (or Supervisor) may view the device status under the ADIO Alarms Detail menu, see 6.5.4.
6.5.3.10Custom Alarms (1-20)
This menu item enables the Supervisor to program 20 separate alarm-triggering equations into the CXC software. The equations may reference any combination (up to 16) of the analog inputs, digital inputs, virtual inputs, and alarms (such as Fan Fail) utilizing logical and arithmetic arguments that simulate the functionality of a programmable logic controller (PLC). See also 7.2 Equation Builder Keypads.
0350046-J0 Rev C |
Page 54 of 127 |
Visit the Alpha website at www.alpha.ca for the latest manual and product downloads
Signal and a Numeric Value Selected
In this example, one signal (V1) and a numeric value (53.50) are selected for the Custom1 alarm to be triggered when [V1] > 53.50. The first operand chosen (top pull-down menu) is Analog Inputs. The next pull-down menu shows that the Supervisor must select from a list of inputs of that type. An operator is selected from the virtual keypad. The keypad is then changed to numeric in order to enter a numeric value to complete the equation.
Name of item being edited |
|
|
|
|
|
|
|
Discard changes and |
|
|
|
|
|
|
|
return to previous screen |
|
|
|
|
|
|
|
|
|
|
Equation displays here |
|
|
|
|
|
|
||
Use slider to navigate/view |
|
|
|
Sliders and scroll bars |
||||
as required |
|
|
|
|||||
|
|
|
are used for navigation |
|||||
|
|
|
|
|
|
|
|
|
Whenever CUSTOMIZE is |
|
|
|
|
||||
selected, a keypad enables |
|
|
|
|
||||
editing of the equation. |
|
|
|
|
||||
(similar to the virtual |
|
|
|
|
|
Accept changes and |
||
numeric keypad) |
|
|
|
|
|
return to previous screen |
||
|
|
|
||||||
Figure 43–Custom Alarm screen
Select Customize to program an alarm-triggering equation as described below.
At any time, as required, select the X icon to cancel entry and close window.
1.Inside the first window shown, after Customize is selected, is the equation building area, numeric keypad and other function keys. Select [Op] for operand (pull-down menu of alarms, signals, etc.).
2.Use pull-down menus to locate Analog Inputs: V1.
3.Select signal (e.g. V1) to add to equation builder.
4.Select Sym for arithmetic symbols (e.g. >) and logic operators and continue to build equation.
5.Select 123 to return to numeric keypad. Enter value (e.g. 53.50) to complete equation.
6.When equation is complete, select the check mark icon (in the lower right corner) to accept changes and return to previous window.
These notes correspond to the numbers in the sequence of figures below:
Figure 44–Customize Alarm example
0350046-J0 Rev C |
Page 55 of 127 |
Refer to the back of this manual for Factory Service and Technical Support contact information
Example 1: Add More Rectifiers Alarm
The function of the following equation is to activate a custom alarm when load increases to a point where redundancy is compromised, but before any rectifiers go into power limit.
Enter the equation taking into consideration logic operators and the number and type of brackets used:
[Load Current] > ((([# Acquired Rectifiers]-1)*55)-5.5)
Where 1 is the number of redundant rectifiers, 55 is the max output current of a single rectifier before going into power limit (3kW PFM in this case), and 5.5 is the number of excess amps in the system required for battery float charging, LVD coils or anything that draws current from the rectifiers that is not the load.
Example 2: Generator ON/OFF Control
The function of the following equations will establish a pair of custom alarms that will activate one relay to start a secondary generator and another relay that stops the generator.
2a) Custom Alarm A to start a secondary generator:
( (V2 <= 46) & (D8 = 0) & (D7 = 0) ) | (V2 < 44.5)
When battery is discharged (system voltage (V2) is less than 46V) and primary (D7) and secondary (D8) generators are not on, OR system voltage is very low, activate. This alarm is exclusively mapped to a relay that is used to start the secondary generator.
2b) Custom Alarm B to stop a secondary generator: ( ( I2 <= 6 ) & (V2 > 53) & ( D8=1) ) | ( D7= 1)
When battery is charged (battery current (I2) is low and system voltage (V2) is near normal) OR primary (D7) generator is on, activate. This alarm is exclusively mapped to a relay that is used to stop the secondary generator.
Example 3: AC Voltage Reading in Mixed Rectifier Systems
The following scenario involves a CXC controlling Pathfinder 10kW rectifiers and Cordex 3.6kW rectifiers in a system with 277Vac. The CXC will compute the average AC reading of all rectifiers (for the AC MAINS HIGH/LOW alarms). In a PFM-CXR system, it may be desirable to have a separate AC alarm for each rectifier type.
To create separate alarms, first use the rectifier Phase Mapping feature (6.3.4) to assign each group of rectifiers to a different phase.
NOTE: the three individual phase voltages will no longer apply; instead, the average of the AC input voltage on each system would be given.
Next, disable the regular AC alarms (6.5.3.5).
Finally, create custom alarms using the average phase voltages. Here is one possible equation: ([Average AC Phase R] < 240) | ([Average AC Phase R] > 300)
0350046-J0 Rev C |
Page 56 of 127 |
Visit the Alpha website at www.alpha.ca for the latest manual and product downloads
Scheduler Usage
The controller has basic scheduling capability that is implemented by using a System Time or System Date signal in any customizable equation; used to trigger external events on a timely basis, whether daily or at a specific date.
This is accomplished by using the System Time or System Date signal as an operator in a Custom Alarm equation, which has been configured to change the state of a relay output. The equation can include any other signals such as battery current or voltage for more advanced control. The System Time or System Date signal can only be used with the following operators: >, <, and =.
NOTE: the formats used for the Time and Date Operands are very specific and must match exactly in order for an equation to be valid. For the System Time the format is <hh.mm.ss>> and for System Date the format is <<20YY.MM.DD>>. The '20' prefix for the year is what distinguishes the date from the time so it must not be omitted when entering a Date Operand.
Example 1: The following equation in a Custom Alarm will cause the alarm to be true for ten seconds (10s) at 2:35AM:
[System Time (HH.MM.SS)] > <<02.35.00>> & [System Time (HH.MM.SS)] < <<02.35.10>> If the alarm is mapped to a relay, the relay will activate for 10s.
Example 2: Another example activates the alarm daily at 23:59:45 and clears when the battery voltage is less than 46V. This is the equation for the alarm named Custom 2:
(([System Time (HH.MM.SS)] > <<23.59.45>>) | ([Custom 2] > 0)) & ([Battery Voltage] > 46)
Note the term: ([Custom 2] > 0). This is to latch the alarm ON since the term: ([System Time (HH.MM.SS)] > <<23.59.45>>) will evaluate to false once the midnight rollover* (<<00.00.00>>) happens.
*Midnight Rollover is described with an example under Custom Signals.
Example 3: We can use the previous example along with a Counter to set the alarm to activate every three days. These are the equations for Counter 1:
Count Event "[System Time (HH.MM.SS)] > <<01.00.00>>" Reset Event "[Counter 1]>2"
The will cause Counter 1 to count once daily at 01.00.00. When the count gets to three, it is immediately reset back to zero. So, every third day, the count returns to zero.
Our Custom 2 alarm equation can now be:
(([System Time (HH.MM.SS)] > <<23.59.45>>) | ([Custom 2] > 0)) & ([Battery Voltage] > 46) & ([Counter 1] = 0)
The resulting behavior will be similar to that in Example 2, except the alarm will only activate once every 3 days.
0350046-J0 Rev C |